LinDistFlow

LinDistFlow is a linearized power flow approximation for radial distribution feeders. It computes bus voltages and branch power flows using a single backward/forward sweep — no iteration required.

Formulation

The DistFlow equations for a radial feeder branch (ij)(i \to j) with impedance r+jxr + jx:

Pj=PijrijPij2+Qij2Vi2P_j = P_{ij} - r_{ij} \cdot \frac{P_{ij}^2 + Q_{ij}^2}{V_i^2}
Qj=QijxijPij2+Qij2Vi2Q_j = Q_{ij} - x_{ij} \cdot \frac{P_{ij}^2 + Q_{ij}^2}{V_i^2}
Vj2=Vi22(rijPij+xijQij)+(rij2+xij2)Pij2+Qij2Vi2V_j^2 = V_i^2 - 2(r_{ij} P_{ij} + x_{ij} Q_{ij}) + (r_{ij}^2 + x_{ij}^2) \cdot \frac{P_{ij}^2 + Q_{ij}^2}{V_i^2}

The linearized approximation drops the quadratic loss terms:

Vj2Vi22(rijPij+xijQij)V_j^2 \approx V_i^2 - 2(r_{ij} P_{ij} + x_{ij} Q_{ij})

Two-Pass Algorithm

  1. Backward sweep (leaves → root): Sum demands at each node to compute branch power flows

  2. Forward sweep (root → leaves): Propagate voltage drops from the source using linearized equations

Transformer Support

For transformer edges with turns ratio aa and impedance zz, the voltage drop includes the turns ratio:

Vj=ViarP+xQVi/aV_j = \frac{V_i}{a} - \frac{r \cdot P + x \cdot Q}{V_i / a}

Usage

from gdm_flow import solve_lindistflow

result = solve_lindistflow(system)

print(f"Success:    {result.success}")
print(f"Source bus:  {result.source_bus}")

# Total source injection
source_p = sum(result.p_net_w.values())
print(f"Source P:   {source_p:.1f} W")

With Custom Injections

from gdm_flow import (
    build_lindistflow_net_injections_from_components,
    solve_lindistflow,
)

# Build default injections, then modify
p_net, q_net = build_lindistflow_net_injections_from_components(
    system,
    include_loads=True,
    include_solar=True,
    include_battery=True,
    include_capacitor=True,
)

# Add a custom 2 kW load
p_net[("bus_3", "A")] = p_net.get(("bus_3", "A"), 0.0) + 2000.0

result = solve_lindistflow(system, p_net_w=p_net, q_net_var=q_net)

Result Object

LinDistFlowResult contains:

FieldTypeDescription
successboolWhether the solve completed
messagestrStatus message
source_busstrName of the source/root bus
voltage_vdict[BusPhaseLabel, float]Bus-phase voltage magnitudes (V)
p_flow_wdict[BranchPhaseLabel, float]Branch active power flows (W)
q_flow_vardict[BranchPhaseLabel, float]Branch reactive power flows (var)
p_net_wdict[BusPhaseLabel, float]Net active power at each bus (W)
q_net_vardict[BusPhaseLabel, float]Net reactive power at each bus (var)

Sign Convention

Limitations

Center-Tapped Transformer Support

LinDistFlow traverses the GDM directed graph (not the Y-bus) and handles center-tapped transformers natively through the edge-based voltage drop propagation. All loads downstream of split-phase service transformers are included in the backward sweep. Unlike DC OPF, LinDistFlow does not rely on a small-angle approximation and correctly models power flow through center-tapped transformers.